Parameter list
Contractor, mixer circuit in
the KM
This is found at control level 2 → Contractor → Mixer 1
Parameters
Setting range Factory setting
MI01
Min. mixer circuit temp 0
°C
- 80
°C
0
°C
MI02
Max. mixer circuit temp 20
°C
- 80
°C
50
°C
MI03
Heating curve gap 0 K - 30 K 10 K
MI04
Screed drying 0 (OFF) - 2 0
MI05
No function - ----
MI06
Run-on time, heating circuit 0 - 30 min 5 min
MI07
P range, mixer 5 K - 40 K 12 K
MI08
Set return temperature 20
°C
- 80
°C
30
°C
MI09
Max. cylinder heating time 0 - 5 h 2 h
MI10
BUS feed (1 = ON)
0 (OFF) - 2 (Auto)
2
MI11
Hysteresis, bypass sensor 0
°C
- 30
°C
10
°C
MI12
Primary pump, blocking 0 - 1 0
MI13
Primary pump, run-on time 0 - 10 min 3 min
MI14
Constant temperature 50
°C
- 80
°C
75
°C
MI15
dT OFF (stop differential) 3 - 20 K 5 K
MI16
dT ON (start differential) 5 - 30 K 10 K
MI17
Boiler overtemperature during
cylinder heating
0 - 40 K 10 K
MI18
Burner blocked during
return temperature raising
0 s 0 s
MI50
Test function 1 - 8 1
Display of the input sensor values
MI70
Analogue input E1 - -
MI71
Analogue input E2 - -
MI72
Analogue input, ow sensor - -
List of parameters MM