Parameters / Function description
KM 27 Set boiler value
and
KM 28 Set boiler value
hysteresis
and
KM 29 Set buffer value
and
KM30 Set buffer value
hysteresis
a) Return temperature raising, wood burning boiler:
The mixer control unit (mixer, return temperature raising and
mixer circuit pump) transfers the energy from the wood burning
boiler into the buffer, and at the same time regulates the return
temperature. The control acts like the mixer circuit control unit;
see also parameter description MI 07.
Mixer circuit pump control:
Mixer circuit pump MKP "ON":
Actual (wood burning) boiler temperature (E1) > KM 27 and
actual header temperature < KM 03 – 2 K
Mixer circuit pump MKP "OFF":
Actual (wood burning) boiler temperature (E1) ≤ KM 27 – KM 28
or actual header temperature > KM 03
b) Changeover between buffer and Wolf boiler by means of
a three-way diverter valve (= 3WUV):
Whether the heating or cylinder circuits are supplied by the
buffer or by the Wolf boiler depends on the position of the three-
way diverter valve. The heating and cylinder circuit demands
are exclusively issued by additional mixer modules.
Position 3WUV AB A (= control 3WUV):
- in case of heating demand and actual header temperature >
KM 29
- in case of cylinder demand
1)
and actual header temperature >
set header temperature
Position 3WUV AB B:
- heating demand ends or actual header temperature ≤
KM 29 – KM 30
- cylinder demand
1)
ends or actual header temperature ≤
set header temperature - 2 K
With outside sensor frost protection, the 3WUV always remains
in position AB B
1)
Also applicable to cylinder frost protection
Conguration KM 01=13