The boiler sequence (A, b, C, d) is selected with the “Selection
boiler sequence” parameter.
Setting A:
The boiler sequence selected under "Boiler sequence A" applies.
Setting b:
The boiler sequence selected under "Boiler sequence b" applies.
Setting C:
Automatic change of boiler sequence A and b (see parameter km 08).
Setting d:
Every boiler automatically becomes lead boiler in rotation after
expiry of parameter km 08.
The boiler sequence is determined by assigning the BUS
addresses.
Every boiler in the cascade has its individual BUS address (1 to
4). The cascade module automatically recognises the number
of connected boilers.
The sequence in which boilers are started and shut down is
selected by boiler sequence A (parameter Km 13) or by boiler
sequence b (parameter Km 14).
For this, see "Setting the eBUS address for Wolf boilers"
KM 12 Selection
boiler sequence
KM 12
8
Factory setting: d
Setting range: A, b, C, d
Individual settings: _________
KM 13 Boiler sequence A The boiler sequence is changed [1, 2, 3, 4, 5] (factory setting)
with the "Boiler sequence A" parameter.
KM 14 Boiler sequence b The boiler sequence is changed [5, 4, 3, 2, 1] (factory setting)
with the "Boiler sequence b" parameter.
Parameters / Function description