MI 02 maximum
mixer circuit temperature
The maximum mixer circuit temperature limits the set ow
temperature of the mixer circuit upwards, for example to prevent
damage to oor coverings.
This does not replace the maximum thermostat for pump
shutdown.
MI 03 Heating curve gap The heating water temperature will be raised by the set value
against the mixer circuit temperature.
MI 01 minimum
mixer circuit temperature
This minimum mixer circuit temperature limits the low end of the
set mixer circuit ow temperature.
With the r.h. rotary selector, choose the mixer parameter to be
modied (MM..) from the contractor menu level (after entering
the correct code).
The mixer parameter to be modied (MM..) is changed by pressing
(display indication ashes) and then turning the r.h. rotary selector.
After setting the mixer parameter to be modied (MM..), pressing
the r.h. rotary selector again conrms the setting.
Pressing the Info pushbutton returns the standard display.
Parameters / Function description