3062449_030950
Set header temperature in [°C]
Set header frost protection
Input in [V]
KM 31 Operating mode
0 - 10 V input
Conguration KM 01 = 12
When using system conguration 12, the external voltage
signal at the 0 - 10 V input of the cascade module is used as
command variable.
In addition, parameter KM 31 determines whether the command
variable is used either
a) to default the modulation level (KM31=1, factory setting, or
a) to default the set header temperature (KM31=2).
Important information regarding function and display values in the KM and BM
KM31 = 1 KM 31 = 2
Header frost protection no yes
Max./min. header temperature
KM 03 / KM 04
no yes
Soft start no yes
Set hysteresis - header temperature
no yes
Modulation stop KM 19 / KM 20 no yes
Outside temperature sensor no AF required no AF required
Display set header temperature
5 °C if the system is set to
"OFF" 99 °C in case of demand
subject to demand
Control deviation display KM 60 ---- current value
Cascade control unit see description parameter KM 15 / KM 16
Transfer curve for KM 31 = 1
Transfer curve for KM 31 = 2
Parameters / Function description
Overall modulation level in [%]: KM61
Input in [V]