MI 08 Set return
temperature
Conguration
km 01 = 7
The return temperature is permanently monitored. If the return
temperature falls too low, all mixers will be forced to raise the
return temperature.
Falling return temperature:
RL_ist < RL_Set + hysteresis, return temperature all mixers
towards "CLOSE"
RL_ist < RL_Set mixer towards "CLOSE" and all heating circuit
and cylinder primary pumps "OFF"
Rising return temperature:
RL_ist < RL_Set + 2 K all mixers towards "CLOSE"
RL_ist < RL_Set + hysteresis, return temperature + 4 K no
forced output
Hysteresis, return temperature = 8 K
MI 07 Mixer circuit
proportional range
Subject to application, the mixer circuit controller can be congured
for the mixer circuit in the heating ow or for the mixer circuit
for return temperature raising. The mixer circuit temperature is
regulated to the set value by means of the mixer circuit sensor /
return temperature sensor (mixer circuit in the heating ow / mixer
circuit for raising the return temperature) via terminal VF and a
motorised mixer. The output of the mixer controller for regulating
the mixer motor features P characteristics. The P range can be
adjusted for each parameter "Proportional range, mixer".
The impulse duration (= activation of mixer motor) is directly
proportional to the mixer ow deviation (T = Set - Actual).
Parameter
MI 07 determines the temperature deviation, for which
the pulse duration is 100%. Outside this range the mixer is either
not regulated at all (T < 1 K) or is regulated constantly (T > as
setting for par. MI 07) headed for. Within the temperature range,
the system exerts constant control. Adjust the proportional range
so that stable regulation is ensured. This depends on the runtime
of the mixer motor. For mixer motors with a short runtime, select
a wide proportional range and vice versa for mixer motors with
longer runtimes, select a narrower proportional range.
Setting information: These settings are only approximate
guidelines.
Change factory settings only where required.
Mixer runtime in min. 2 - 3 4 - 6 7 - 10
Temperature window in K
MI 07
25 - 14 15 - 9 10 - 5
MI 06 Mixer circuit pump
run-on time
The mixer circuit pump / heating circuit pump will run on according
to the set value after the mixer circuit / heating circuit has been
switched OFF.