Additional functions / Reset
The set cylinder temperature is 10 °C when cylinder heating is
blocked. Cylinder frost protection is activated when the actual
cylinder temperature < set cylinder temperature - 5 K. The
set ow temperature then results from the set cylinder
temperature + parameter MI 17.
Cylinder frost protection
Emissions test enabled ⇒ Central heating and DHW heating
are enabled until the emissions test has been completed.
During the emissions test of a boiler, other heating circuits in a
cascade remain OFF.
Emissions test
The mixer will be regulated to drive to "OPEN" for approx. 10
seconds daily (12:00 h at the cascade module) and then for 20
seconds to "CLOSE" to prevent the mixer from seizing up as a
result of prolonged idle times; subject to conguration (KM 01) =
1/2/3/5/7/8, the mixer is driven for 10 seconds towards bypass
"CLOSE" followed by 20 seconds towards bypass "OPEN".
Conguration = 6/13.
Anti-seizing mixer
protection
To prevent the pumps from seizing because of long idle periods,
the mixer circuit pump MKP and output A1 will be activated daily
for approximately ve seconds (12:00 h at the cascade module)
after they have been idle for more than a day.
Anti-seizing pump
protection
The header is protected against frost if the program selector is
set to "Standby" or "Summer mode". The burner will be enabled
if the header temperature falls below 5 °C. All heating circuits
and primary pumps are started at the cascade module, and the
set mixer circuit temperature (if a mixer circuit is installed at the
KM) of the KM are regulated to a ow temperature of 40 °C. The
header frost protection functions ends if the header temperature
rises above 20 °C.
The frost protection of the header does not apply if system
conguration 13 has been selected.
Header frost protection
Loading the standard values
(Reset)
Set DIP 4 to "OFF" and then back to "ON". The standard values
are now loaded again.
All LEDs illuminate briey as conrmation.
Fault message input If the jumper at the fault message input is open, FC 79 is
displayed by the BM and the entire system is shut down
(= no heat demand).