Wolf FB363 Instruções de Operação Página 51

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 60
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 50
3062449_0309 51
KM 50 Test function Parameter KM50 enables the individual control of the relays.
KM50 = 1  Control, mixer circuit pump relay MKP
KM50 = 2 Control, mixer motor relay "OPEN" MM
KM50 = 3 Control, mixer motor relay "CLOSE" MM
KM50 = 4 Control, relay output A1
KM 60 Control deviation Indicates the control deviation = set header temperature - actual
header temperature.
KM 61
Overall modulation level
Indicates the overall modulation level.
No display if system conguration 13 and 4 has been selected.
KM 62 Modulation level,
boilers
a) Modulating boilers, if KM 02 = 3:
Indicates the modulation level or all active boilers.
b) Single stage boilers, if KM 02 = 1:
KM 62 = 0% no boiler active
KM 62 = 100% boiler 1 with address 1 active
If an additional boiler is controlled, the KM 62 always shows 100%.
c) Two-stage boilers, if KM 02 = 2:
KM 62 = 0% no boiler active
KM 62 = 50% stage 1 of boiler with address 1 active
KM 62 = 100% stage 2 of boiler with address 1 active
If an additional boiler/stage is controlled, the KM 62 always
shows 100%.
No display if system conguration 13 and 4 has been selected.
Parameters / Function description
Vista de página 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 59 60

Comentários a estes Manuais

Sem comentários