c) For two-stage boilers (KM 02 = 2; KM 15 and KM 16 exert
no inuence)
With two-stage boilers, the second stage is treated as if it were
a boiler in its own right that is always started after stage 1 and is
always shut down prior to stage 1 of that boiler.
Load split for two-stage boilers:
Stage 1 = 67%
Stage 2 = 33%
Soft start phase:
"See single stage boilers"
Additional information regarding the cascade algorithm for single stage and
two-stage boilers in conjunction with conguration 12 and parameter KM 31 = 1
In this case, the following functions do not apply:
a) Shutdown condition for the boiler started last, if the
"actual header temperature > set header temperature
+ 1 K".
b) Shutdown condition of the lead boiler if the "actual
header temperature > set header temperature +
header temperature hysteresis".
c) no soft start
Parameters / Function description