Start enabling/start blocking for the lead boiler:
- Start enabling:
Boiler temperature, lead boiler >
actual header temperature + hysteresis, modulation stop
- Start enabling:
Boiler temperature, lead boiler <
actual header temperature + 5 K
Hysteresis modulation stop KM 20 adjustable from 10 K to 50 K.
Blocking/Enabling I portion, overall modulation:
- Blocking I portion:
Boiler water temperature
1)
>
actual header temperature + hysteresis, modulation stop
- Enabling I portion:
Boiler water temperature
1)
<
actual header temperature + 5 K
1)
Boiler that was started last.
Note: The "Cascade controller stop" function should only
be enable if no cylinder is connected to boiler with address 1.
For systems without low loss header, e.g. systems that
are operated on the inlet side, also enable the "Pump control,
lead boiler" function.
KM 21 Forced output for
cylinder heating
and
KM22 Parallel mode
hysteresis
For systems where the overall output of all boilers was not
sized for peak loads in parallel operation of central and DHW
heating, there remains the possibility that the required
set header temperature is not achieved during cylinder heating
at peak load times. To prevent this, the energy supply to the
mixer circuits is reduced via forced output. The following
conditions must be met for "Cylinder priority in parallel mode":
a) Parameter KM 21 = 1
"Forced output during cylinder heating" function enabled
b) and parameter "Contractor/System" A10 = 1
parallel mode "ON";
c) and all boilers of the cascade operational
d) and overall modulation level = 100%
e) and cylinder heating at the cascade module
(KM 01 = 1 or 10) enabled