b) For single stage boilers
(KM 02 = 1; KM 15 and KM 16 exert no inuence)
Starting boilers:
Boiler 1 is started when the overall modulation level is > 0.
An additional boiler will be started if the internal algorithm
from the resulting overall modulation level calculates that an
additional output stage should be started and the blocking time
has expired. In this case, the blocking time will be invoked.
Shutting boilers down:
The boiler started last will be stopped when the internal
algorithm from the resulting overall modulation level has
calculated that an output stage should be shut down or if
the set temperature has been exceeded by 1 K. In this case,
the blocking time will be invoked. An additional boiler will be
shut down if the internal algorithm from the resulting overall
modulation level calculates that an output stage should be shut
down.
The nal boiler will be shut down when the actual header
temperature > set header temperature + header temperature
hysteresis.
Soft start phase:
Soft start only applies to the lead boiler and not to the starting of
additional boilers. It also applies if only one boiler is connected
to the KM. Once the blocking time has expired and the overall
modulation level > 0, the I portion will be blocked for the
calculation of the overall modulation level within the rst three
minutes. Soft start ends after the expiry of three minutes or
after the actual header temperature > set header temperature +
header temperature hysteresis.
Parameters / Function description
Additional information regarding the cascade algorithm for modulating boilers
in conjunction with conguration 12 and parameter KM 31 = 1
In this case, the following functions do not apply:
a) Shutdown conditions for an additional boiler, if the
"actual header temperature > set header temperature
+ 1 K".
b) Shutdown condition of the lead boiler if the "actual
header temperature > set header temperature +
header temperature hysteresis".
c) No soft start