MI 04 Screed drying If an under oor heating system is started for the rst time in new
buildings, the set ow temperature may, as an option, be controlled
independent of the outside temperature either to a constant value or
to control the set ow temperature in accordance with an automatic
screed drying program.
If this function has been enabled (setting 1 or 2), it can be terminated
by resetting parameter MI 04 to 0.
MI 04 = 0 without function
MI 04 = 1 constant temperature mixer circuit
The mixer circuit is heated to the set ow temperature. The set
ow temperature is permanently set to the temperature selected
in parameter MI 01.
MI 04 = 2 screed drying function
For the rst two days, the set ow temperature will remain constant
at 25 °C. It will then be automatically raised every day (at 0:00 h)
by 5 °C up to the maximum mixer circuit temperature (MI 02).
That temperature will then be held for two days. Subsequently,
the ow temperature is automatically reduced again in 5 °C steps
per day to 25 °C. The program sequence is terminated after a
further two days.
Fig.:
Flow temperature progress
over time during screed
drying
Flow temperature (°C)
Screed drying runtime (days)
NB:
Agree the time sequence and the maximum ow temperature with
the screed contractor, otherwise the screed may be damaged,
particularly through cracking.
The screed drying program continues after a power failure. The
remaining time in days is displayed at the BM.